Regulasi suhu PID

Dalam aplikasi seluler, Anda dapat mengonfigurasi 3 parameter utama – P, I, D.

ErrorSetPoint – Current Temperature

Time from last update
Time since last update in minutes.
PSet by userIf P is equal to 10 and Error is 1C then the resulting output will be equal to 10%.
ISet by userIf I is equal to 1 and the Error is 1C, then the resulting output will grow by 1% every minute.
DSet by userIf D is equal to 1 and the Error has changed from 4C to 2C in 1 minute, then the resulting output will have decreased by 2%.
P GainP * Error
I GainPrevious I Gain + (I * Error * Time from Last updade) x
D GainD * ((error – lastError) / Time from Last updade)
OutputP Gain + I Gain + D GainThe resulting output is the sum of the three gains.